Related Categories:Electrical Plugs & Sockets
Power Strip Extension Socket Surge Protector 1. LDY-CZ/PDU 2. Un: 220V, Uc: 320V, Up: <1.3V 3. In: 5kA, Imax: 10kA 4. Rack

Power Strip Extension Socket Surge Protector

Application range:

LDY-CZ series socket power surge protective devices are applied to the front side of various terminal equipment of AC not more than 220V and rated current less than 10A, providing protection against overvoltage arising from surge to the power supply line and misoperation.(option from standard IEC61643-1 and GB50343).

Main features:

High current capacity, low residual voltage;Modularized design, standard socket design, convenient for installation and use;Introducing multilayer protection technology, strong protection ability, high reliability;Build-in temperature fuse, safe and reliable;Red pilot lamp on indicate normal, off indicate invalid.

Main technical data:

Type

LDY-CZ/PDU

LDY-CZ/06

Nominal operating voltage Un V

220

220

Max. continuous voltage Uc V

320

320

Voltage protection level Up V

< 1.3

< 1.5

Part No.

086201

086202

Rated working current le A

10

Nominal discharge current In (8/20μs) kA

5

Max. discharge current Imax (8/20μs) kA

10

Connection mode

Standard GB three-position socket

Response time tA

< 25ns

Enclosure material

Enhanced flame retardant nylon

(flame retardancy degree: V0)

Method of installation

19” Rackmount

35mm standard DIN rail

Cross-section

2.5 mm2 stranded/flexible conductor

Installation instruction:

The protector connected in parallel between the power channel and the protected device;Connect the input terminal to the power wire or insert the input terminal into the power socket, and then insert the power wire of protected device into socket, make sure the reliable connection;connect the earthing wire of the protector to the equalizing ring of the lightning protection system;if the red indicator light on after circuit be electrified. The lightning protection work is normal.