Socket Surge Protector
Power Strip Extension Socket Surge Protector
Application range:
LDY-CZ series socket power surge protective devices are applied to the front side of various terminal equipment of AC not more than 220V and rated current less than 10A, providing protection against overvoltage arising from surge to the power supply line and misoperation.(option from standard IEC61643-1 and GB50343).
Main features:
High current capacity, low residual voltage;Modularized design, standard socket design, convenient for installation and use;Introducing multilayer protection technology, strong protection ability, high reliability;Build-in temperature fuse, safe and reliable;Red pilot lamp on indicate normal, off indicate invalid.Main technical data:
Type | LDY-CZ/PDU | LDY-CZ/06 |
Nominal operating voltage Un V | 220 | 220 |
Max. continuous voltage Uc V | 320 | 320 |
Voltage protection level Up V | < 1.3 | < 1.5 |
Part No. | 086201 | 086202 |
Rated working current le A | 10 | |
Nominal discharge current In (8/20μs) kA | 5 | |
Max. discharge current Imax (8/20μs) kA | 10 | |
Connection mode | Standard GB three-position socket | |
Response time tA | < 25ns | |
Enclosure material | Enhanced flame retardant nylon (flame retardancy degree: V0) | |
Method of installation | 19” Rackmount | 35mm standard DIN rail |
Cross-section | 2.5 mm2 stranded/flexible conductor |
Installation instruction:
The protector connected in parallel between the power channel and the protected device;Connect the input terminal to the power wire or insert the input terminal into the power socket, and then insert the power wire of protected device into socket, make sure the reliable connection;connect the earthing wire of the protector to the equalizing ring of the lightning protection system;if the red indicator light on after circuit be electrified. The lightning protection work is normal.Socket Surge Protector